Operating ManualXantrex Datacom InverterXDI20482kVA/1.5kW
Contentsviii TM-DIOP-01XN-01CAN/SYNC Connector - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–13Overview - - - - - -
ContentsTM-DIOP-01XN-01 ixFuses and Grounding - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–10Incorrect Connection
ContentsxTM-DIOP-01XN-01ASpecificationsInverter Specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A–2E
TM-DIOP-01XN-01 xiFigure 2-1 Packing List - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–2Figure 2-2 Shipping
TM-DIOP-01XN-01 xiiiTable 2-1 User Line Connection- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–12Table 2-2 CAN/SYNC Pin-o
xiv
1IntroductionChapter 1 contains an introduction to the XDI Inverter and the Ethernet card. This chapter provides a list of the major features, protect
Introduction1-2 TM-DIOP-01XN-01Inverter InformationDescriptionThe Xantrex Datacom Inverter (patent pending) is the most versatile modular rack mounted
Ethernet InformationTM-DIOP-01XN-01 1-3Ethernet InformationDescriptionThe internal XDI Ethernet interface allows you to monitor and operate your inver
Introduction1-4 TM-DIOP-01XN-01Monitor Functions• DSP Firmware Version• Manufacturer•Model• Serial Number• Front Panel LED status• Output Voltage• Out
2Rack Mount Frame Assembly and InstallationChapter 2 contains information and procedures to assemble and install the rack mount, and install the inver
Rack Mount Frame Assembly and Installation2-2 TM-DIOP-01XN-01Initial InspectionWhen you first receive your unit, perform a quick physical check.1. Ins
Initial InspectionTM-DIOP-01XN-01 2-3Packaging for Shipping or StorageFollow these instructions to prepare the unit for shipping or storage.1. When re
Rack Mount Frame Assembly and Installation2-4 TM-DIOP-01XN-01IntroductionYou can use the Inverter in rack-mounted applications. Alternate configuratio
Location, Mounting and VentilationTM-DIOP-01XN-01 2-5Location, Mounting and VentilationWhen you install the Inverter into a rack, allow cooling air to
Rack Mount Frame Assembly and Installation2-6 TM-DIOP-01XN-01Installation into Relay RacksUse the supplied mounting brackets to secure the backplane i
DC Input PowerTM-DIOP-01XN-01 2-7DC Input PowerInput Connector and CablesThe XDI input connector is a 2-pole, double lug terminal block with separate
Rack Mount Frame Assembly and Installation2-8 TM-DIOP-01XN-014. Note the polarity on the input connector as indicated and fasten the positive and nega
AC Load and Signal Line ConnectionTM-DIOP-01XN-01 2-9AC Load and Signal Line ConnectionAC Output ConnectorThis is a two terminal barrier strip for use
Xantrex Datacom InverterXDI2048 2kVA/1.5kWOperating Manual
Rack Mount Frame Assembly and Installation2-10 TM-DIOP-01XN-01Load Connection1. If necessary, remove the output cover by loosening the two securing nu
AC Load and Signal Line ConnectionTM-DIOP-01XN-01 2-11User Line ConnectionOverviewThe User-line interface provides basic remote control and monitoring
Rack Mount Frame Assembly and Installation2-12 TM-DIOP-01XN-01User Line ConnectorThe user-line is a 6-position wire clamp connector adjacent to the DC
AC Load and Signal Line ConnectionTM-DIOP-01XN-01 2-13CAN/SYNC ConnectorOverviewThe CAN/SYNC connector provides access to functions necessary for oper
Rack Mount Frame Assembly and Installation2-14 TM-DIOP-01XN-01CAN/SYNC Wiring Due to high bus speed, use shielded twisted pairs of 22-24 AWG for impro
Connection SchemesTM-DIOP-01XN-01 2-15Connection SchemesStand-Alone OperationA 120 Ohm resistor should be connected across the CAN-hi and CAN-lo termi
Rack Mount Frame Assembly and Installation2-16 TM-DIOP-01XN-01• The AC output load wires are also connected in parallel ensuring only like terminals L
Connection SchemesTM-DIOP-01XN-01 2-17Split Phase OperationUse this scheme to extend the output voltage. No more than two units should be connected in
Rack Mount Frame Assembly and Installation2-18 TM-DIOP-01XN-01Three Phase OperationOverviewXDI inverters can be configured for 3-phase operation where
3-Phase Synchronization and Signal WiringTM-DIOP-01XN-01 2-193-Phase Synchronization and Signal WiringRefer to Table 2-2 for the signal pinouts.To ach
About XantrexXantrex Technology Inc. is a world-leading supplier of advanced power electronics and controls with products from 50 watt mobile units to
Rack Mount Frame Assembly and Installation2-20 TM-DIOP-01XN-013-Phase, 3-Wire Delta Output Wiring• All outputs should be wired through an appropriatel
Ethernet PortTM-DIOP-01XN-01 2-213-Phase, 4-Wire Y-Connection Output WiringThis scheme is the same as the preceding with the addition of a neutral con
3Inverter Module Installation and OperationChapter 3 contains information and procedures for installing and using the XDI Inverter.This chapter descri
Inverter Module Installation and Operation3-2 TM-DIOP-01XN-01Installation into Rack Mount FrameInstalling To install an inverter module, slide it into
Installation into Rack Mount FrameTM-DIOP-01XN-01 3-31. Captive Screw2. Handle3. Power Switch4. Air Intake Vents5. “Fault” and “ON” LED’sUninstalling
Inverter Module Installation and Operation3-4 TM-DIOP-01XN-01Operation of Inverter ModuleTheory of OperationThe XDI is a digitally controlled power co
Operation of Inverter ModuleTM-DIOP-01XN-01 3-5Standby ModeThis low power state allows your inverter to recommence operation quickly but conserves pow
Inverter Module Installation and Operation3-6 TM-DIOP-01XN-01User InterfaceFront PanelUser LinesThe port with user lines is located at the rear panel
Protections and AlarmsTM-DIOP-01XN-01 3-7Protections and AlarmsOverviewThe Digital Signal Processor (DSP) in the inverter continuously monitors a numb
TM-DIOP-01XN-01 iiiAbout This ManualPurposeThe purpose of this Operating Manual is to provide explanations and procedures for installing, operating, m
Inverter Module Installation and Operation3-8 TM-DIOP-01XN-01Overload ProtectionThe inverter will deliver the rated load power continuously at the rat
Protections and AlarmsTM-DIOP-01XN-01 3-9Over Temperature Protection (OTP)This feature protects critical components from failure due to temperature st
Inverter Module Installation and Operation3-10 TM-DIOP-01XN-01Fuses and GroundingThe inverter is equipped with non-user replaceable, internal fuses fo
MaintenanceTM-DIOP-01XN-01 3-11To Clear an AlarmDepending on the cause of the alarm, the alarm may be cleared automatically as soon as the fault condi
3-12Figure 3-4Replacing the Fan Filters2. Remove the Cover1. Unscrew the Cover5. Remove the Fan and Fan Filters4. Remove the Front Panel3. Remove the
4Remote Communication & MonitoringChapter 4 contains information and procedures for using the Ethernet to provide remote communication and monitor
Remote Communication & Monitoring4-2 TM-DIOP-01XN-01IntroductionWhen installed, the optional TCP/IP enabled Ethernet communications card and user
Initial SetupTM-DIOP-01XN-01 4-3Figure 4-1Ethernet Interface PCBImportant:The only way to configure the interface card is through the Ethernet port us
Remote Communication & Monitoring4-4 TM-DIOP-01XN-01How to Setup For the First TimeHardware SetupIn order to communicate to the XDI Ethernet for t
Initial SetupTM-DIOP-01XN-01 4-5Ethernet SetupYou must run a Web browser to communicate and configure the XDI Ethernet. Microsoft Internet Explorer or
About This Manualiv TM-DIOP-01XN-01Chapter 3, “Inverter Module Installation and Operation”, Chapter 3 contains information and procedures for installi
Remote Communication & Monitoring4-6 TM-DIOP-01XN-01You can use Table 4-2 to record your own settings.ResettingTo reset the Ethernet settings the
Initial SetupTM-DIOP-01XN-01 4-7Table 4-3Reset SettingsSetting Reset ValueDefault IP 192.168.1.1Gateway IP 0.0.0.0Sub-Net Mask 255.255.255.0Domain Nam
Remote Communication & Monitoring4-8 TM-DIOP-01XN-01Figure 4-4Ethernet Reset JumperEthernet configurationreset jumper (SW2)
Operating InstructionsTM-DIOP-01XN-01 4-9Operating InstructionsIntroductionThe Ethernet interface card allows you to monitor/configure settings using
Remote Communication & Monitoring4-10 TM-DIOP-01XN-01Figure 4-5Network SetupPCPCDHCP ServerInverterInverterHubPCPCSpecial cross-over cable require
Operating InstructionsTM-DIOP-01XN-01 4-11Using DHCPA DHCP server is used to obtain a dynamic IP that is unique on the network. To enable DHCP, set th
Remote Communication & Monitoring4-12 TM-DIOP-01XN-01PasswordThe Web page interface is password protected. See “Password” on page 4–12 for the def
Operating InstructionsTM-DIOP-01XN-01 4-13Automatic Power-On EmailWhen the inverter is turned on, it will attempt to send an email to the configured “
Remote Communication & Monitoring4-14 TM-DIOP-01XN-01Manage PageThe “Manage page” is the first page of the Web page. It contains information about
Operating InstructionsTM-DIOP-01XN-01 4-15Setup PageThe “Setup page” allows the user to set the Ethernet interface card’s network setting, email setti
TM-DIOP-01XN-01 vImportant Safety InstructionsWARNINGOperate the Inverter in an environment free of flammable gases or fumes. To ensure that the Inver
Remote Communication & Monitoring4-16 TM-DIOP-01XN-01Table 4-5Setup Page of Web InterfaceObject DescriptionMonitor Page Refresh RateThe rate at wh
Operating InstructionsTM-DIOP-01XN-01 4-17Monitor pageThe “Monitor page” shows the current status of the Inverter. It displays the output measurements
Remote Communication & Monitoring4-18 TM-DIOP-01XN-01Table 4-6Monitor Page of Web InterfaceObject DescriptionOutput Voltage Last measured output v
Operating InstructionsTM-DIOP-01XN-01 4-19Automatic Shutdown EmailWhen the inverter shuts down due to a fault or a user shutdown, the Ethernet interfa
Remote Communication & Monitoring4-20 TM-DIOP-01XN-01Important:Refer to “Protections and Alarms” on page 3–7 for a more detailed description of fa
5TroubleshootingChapter 5 contains information and procedures for troubleshooting your XDI Inverter and Ethernet card.
Troubleshooting5-2 TM-DIOP-01XN-01User DiagnosticsIf your XDI is not performing as described in this manual, run through the procedures and checks in
User DiagnosticsTM-DIOP-01XN-01 5-3Diagnostic GuideITable 5-1Inverter DiagnosticsSymptom Check Further Checks and CorrectionsNo output. No front panel
Troubleshooting5-4 TM-DIOP-01XN-01Table 5-2Ethernet DiagnosticsSymptom Check Further Checks and CorrectionsIP address doesn’t work 1. Static IP alread
A SpecificationsAppendix A supplies information about specifications for the XDI Inverter and the Ethernet.
vi
SpecificationsA-2 TM-DIOP-01XN-01Inverter SpecificationsElectrical SpecificationsInput Voltage, Current, Power, Frequency RangesOutput Voltage, Curren
Inverter SpecificationsTM-DIOP-01XN-01 A-3Power Factor • linear – powers all loads with 0 leading to 0 lagging PF• stable with constant power type loa
SpecificationsA-4 TM-DIOP-01XN-01Efficiency • Minimum 85% efficiency at full power, peak efficiency 89%• No load draw: less than 60 WStart Up Behavior
Inverter SpecificationsTM-DIOP-01XN-01 A-5Mechanical SpecificationsVentilation Air intake from front of unitNo additional clearance required top or bo
SpecificationsA-6 TM-DIOP-01XN-01DimensionsWeight Inverter: 22 lbs. (10kg)Rack Mount Frame: 6 lbs (2.7 kg) with sliding railsFigure A-1Inverter and Ra
Ethernet SpecificationsTM-DIOP-01XN-01 A-7Ethernet SpecificationsSpecifications The specifications in this section are warranted at 25°C ± 5°C unless
TM-DIOP-01XN-01 B-1Warranty and Product InformationWarrantyWhat does this warranty cover? This Limited Warranty is provided by Xantrex Technology, Inc
WarrantyB-2 TM-DIOP-01XN-01What proof of purchase is required? In any warranty claim, dated proof of purchase must accompany the product and the produ
Return Material Authorization PolicyTM-DIOP-01XN-01 B-3ExclusionsIf this product is a consumer product, federal law does not allow an exclusion of imp
TM-DIOP-01XN-01 viiImportant Safety Instructions1IntroductionInverter Information - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
WarrantyB-4 TM-DIOP-01XN-01Return Procedure1. Package the unit safely, preferably using the original box and packing materials. Please ensure that you
Xantrex Technology Inc.1 800 670 0707 Tel toll free NA1 360 925 5097 Tel direct1 800 994 7828 Fax toll free NA1 360 925 5143 Fax directcustomerservice